Back to Resources
Technology7 min read

Waste Heat Recovery: A Primer for Data Center Operators

How waste heat recovery works and why it's becoming essential for facilities with on-site power generation.

Data centers with on-site power generation face a unique opportunity: converting waste heat from prime movers into useful cooling power. As grid interconnection delays stretch into multi-year timelines and behind-the-meter generation becomes standard practice, waste heat recovery transforms from a theoretical efficiency gain into a strategic necessity.

This primer explains how waste heat recovery works, the technologies available, and why facilities with on-site power are uniquely positioned to capture this value.

The Waste Heat Opportunity in Data Centers

Understanding the Thermal Resource

On-site power generation—whether reciprocating engines, fuel cells, or microturbines—converts fuel chemical energy into electricity with typical electrical efficiencies of 35-45%. The remaining 55-65% of input energy becomes waste heat, rejected through exhaust gases (300-500°C), engine cooling systems (80-120°C), and radiative losses.

For a 10 MW natural gas reciprocating engine operating at 40% electrical efficiency, approximately 15 MW of thermal energy becomes waste heat. Conventional approaches reject this energy to the atmosphere—a massive missed opportunity when the same facility may consume 3-5 MW of electrical power for mechanical cooling.

The Scale of the Opportunity

Data centers typically allocate 30-40% of non-IT electrical load to cooling infrastructure. For facilities with on-site generation, this creates a direct arbitrage opportunity: capture waste heat that would otherwise be rejected, convert it to cooling power, and offset electrical consumption.

The economics are compelling. Each kW of cooling capacity produced from waste heat eliminates approximately 0.2-0.3 kW of electrical load (depending on mechanical chiller efficiency), improving overall facility efficiency, reducing fuel consumption, and enhancing operational resilience.

Waste Heat Recovery Technologies for Cooling

Three primary technology families convert low-to-medium grade waste heat into cooling power, each with distinct performance characteristics and application constraints.

Absorption Chillers: The Established Option

Absorption cooling has served industrial applications for decades, using thermal energy to drive a chemical absorption cycle that produces chilled water. Lithium bromide-water (LiBr-H₂O) absorption chillers operate with heat input temperatures of 80-95°C, making them compatible with engine jacket water cooling systems.

Performance Characteristics

Coefficient of Performance (COP):0.6-0.7 for single-stage systems
Heat input temperature:80-95°C for single-stage, 120-150°C for double-stage
Typical capacity:100 kW to multi-MW scales

Operational Considerations

  • Requires cooling towers for heat rejection (water consumption)
  • LiBr solution is corrosive, requiring specialized materials and maintenance
  • Performance degrades significantly at high ambient temperatures
  • Crystallization risk if heat input varies or solution chemistry isn't maintained
  • No backup operating mode—if waste heat is unavailable, system cannot provide cooling
  • Provides no value during economizer hours when ambient air cooling is used

Adsorption Chillers: Reduced Maintenance, Similar Constraints

Adsorption cooling uses physical adsorption onto solid materials (typically silica gel or zeolites) rather than chemical absorption, eliminating the corrosive solution maintenance burden. Commercially available from manufacturers including Hitachi, Johnson Controls, and Mayekawa.

Performance Characteristics

COP:0.5-0.68 depending on heat source temperature
Heat input temperature:50-95°C (140-176°F)
Chilled water outlet:41°F suitable for data centers
Maintenance:Lower than absorption (no corrosive working fluids)

Research demonstrates payback periods as low as 285-379 days for appropriately sized installations. However, like absorption chillers, their dependence on continuous waste heat availability and water consumption limit operational flexibility.

Organic Rankine Cycle (ORC): Power Generation Alternative

Rather than producing cooling directly, ORC systems convert waste heat into electrical power through a closed-loop thermodynamic cycle using organic working fluids with low boiling points. This electricity can then power conventional mechanical chillers.

Performance Characteristics

Thermal-to-electric efficiency:3-7% for low-grade heat (45-120°C)
Higher temperature sources:10-15% efficiency (150-300°C)
PUE impact:Does not improve—only expands available electrical power

ORC systems offer flexibility—generated electricity can serve any facility load—but the double conversion penalty (heat → electricity → cooling) limits effectiveness compared to direct thermal cooling approaches.

Integrated Waste Heat-to-Cooling: A Proven Approach

After over a decade of federally-funded development, integrated waste heat-to-cooling systems combine the power generation and cooling cycles into a single thermodynamic system, eliminating the efficiency losses from separate ORC and chiller components.

These systems use a directly-coupled turbo-compressor where the same shaft simultaneously extracts power from an organic Rankine cycle and drives a vapor compression refrigeration cycle. The technology has been validated through extensive testing with DOE, ARPA-E, and DOD funding.

Performance Advantages

Thermal COP:Approaching 1.0 for data center applications due to higher chilled water delivery temperatures
Demonstrated COP:0.56 in general applications (increases with higher return temperatures)
Water consumption:Zero—air-cooled operation
Refrigerants:Non-toxic, non-corrosive (e.g., R1234ze(E))

Operational Benefits

  • Hybrid operation modes: thermal-only, electric-boosted, or power generation—providing backup capability
  • No water consumption (critical for water-constrained regions)
  • Maintains efficiency in high ambient temperatures where absorption degrades
  • Lower maintenance burden than absorption systems
  • Can operate during economizer hours in hybrid mode if needed

Impact on Data Center Efficiency Metrics

Power Usage Effectiveness (PUE)

By recovering 50-60% of engine waste heat for cooling, facilities can reduce electrical cooling loads by 15-25%, improving PUE from typical values of 1.4-1.5 down to 1.2-1.3 or better. Studies demonstrate that ORC-based waste heat recovery systems can reduce PUE by 5-6%.

Energy Reuse Effectiveness (ERE)

ERE metrics directly credit waste heat recovery by reducing the numerator in the ERE calculation: (Total Facility Power - Reused Energy) / IT Equipment Power. Facilities converting waste heat to cooling achieve ERE values significantly below their PUE.

Water Usage Effectiveness (WUE)

Air-cooled waste heat recovery eliminates water consumption for both heat rejection and cooling production, achieving WUE of zero—a critical advantage in water-constrained regions. This contrasts sharply with absorption chillers requiring cooling towers.

Carbon Usage Effectiveness (CUE)

While on-site generation produces direct combustion emissions, waste heat recovery reduces total fuel consumption per unit of IT load by maximizing useful energy extraction. Fuel consumption decreases of 12-20% translate directly to proportional CO₂ emission reductions.

Key Takeaways

  • On-site generation creates 55-65% waste heat that can be captured for cooling production
  • Absorption/adsorption chillers are established but require water and have operational constraints
  • ORC systems generate electricity but don't directly improve PUE
  • Integrated turbo-compressor systems combine power and cooling cycles for maximum efficiency
  • Air-cooled waste heat recovery achieves zero WUE while improving PUE
  • Hybrid operation modes provide flexibility and backup capability

Powerdrive Thermal's turbo-compressor technology represents over a decade of federally-funded development, specifically optimized for data center applications where water consumption, operational simplicity, and ambient temperature resilience are critical design parameters.

— Powerdrive Thermal

References & Further Reading

Ready to Learn More?

Discover how Powerdrive can help transform your data center's energy efficiency.

Get in Touch